Boiler KC "EFFECT".

Back >>>

- Is issued in three versions: on firm fuel KCU-A, on gaseous KCU-Gn and liquid KCU-LJ;
- For the best selection by the heat-carrier three-running movement of products of combustion of fuel (instead of two boilers of an old design) is used;
- Boilers are delivered in gas dense execution that allows in versions KCU-Gn and KCU-LJ to use modern fan torch the devices working at positive pressure in boiler;
- The overall performance of the boiler in gas dense execution is higher 3-4 %.



  The name of a parameter UnitExecution of the boiler
KCU-3 KCU-4 KCU-5 KCU-6 KCU-7
1 Nominal productivity of heat,
Not less
-On anthracite
-On Gas
-On liquid fuel
KW

20
32
32


31
47
47


42
63
63


52
80
80


63
90
90
2 Quantity sections   3 4 5 6 7
3 Efficiency
-On anthracite
-On Gas
-On liquid fuel
%
77,5
90,5
90,5

78
91
91

79
91
91

79
91
91

79,5
91
91
4 Weight of the boiler, No more kg 435 540 640 754 860
5 The charge of fuel:
-for KCU-Gn
-for KCU-LJ

m³/h
kg/h

3,7
3,2

5,6
4,5

7,5
6,0

9,4
7,6

11,0
8,6
6 Working pressure of water, No more MPa 0,4


The operation manual on the boiler "EFFECT" (.rar)   >>>